FMR‑7036 Fire Annunciator Keypad

FMR‑7036 Fire Annunciator Keypad

  • Compatible with FPD‑7024 Fire Alarm Control Panel
  • Two‑line, 16‑character LCD display
  • On‑board LEDs indicate Silenced, Trouble, Alarm, and Supervisory
  • Silence and Reset buttons
  • Built‑in keyswitch
  • Attractive, low‑profile enclosure
  • UL Listed

The FMR‑7036 is a four‑wire LCD annunciator keypad used with the FPD‑7024 Fire Alarm Control Panel (FACP) to establish the location of a fire alarm. The two‑line, 16‑character display is capable of showing all messages normally displayed on the control panel. All alarm and status messages are included. Four on‑board LEDs provide easy reading of the annunciator's status from a distance. There are Silence and Reset buttons for controlling annunciator and control panel operation. A built‑in keyswitch offers extra security by locking the annunciator to prevent unwanted sounder silencing or control panel resetting.

   
Environment: Indoor, dry
Relative Humidity: Up to 95%, non‑condensing
Temperature (operating): +32°F to 120°F (0°C to +49°C)
   
Base Dimensions (HxW): 4.6 in. x 8.2 in. (11.7 cm x 20.8 cm)
Cover Dimensions (HxW): 4.3 in. x 8.1 in. (10.9 cm x 20.6 cm)
   
Current (Alarm): 100  mA
Current (Standby): 80 mA nominal
Voltage (Operating): 12 VDC nominal