FPC‑7034 Four-Point Expander

FPC‑7034 Four-Point Expander

  • Adds four Class B (Style B) or Class A (Style D) initiating circuits to the FPD‑7024 FACP
  • For use with normally‑open (NO) or normally‑closed (NC) alarm contacts
  • Compatible with two‑wire or four‑wire smoke detectors
  • Up to 20 two‑wire smoke detectors per circuit
  • Easy installation due to plug‑in design and screw terminal circuit connections
  • No programming necessary

The FPC‑7034 Four-point Expander doubles the number of alarm initiating device circuits on the FPD‑7024 Fire Alarm Control Panel (FACP). These circuits are identical to the circuits on the FACP. This plug‑in module is automatically recognized by the control panel's firmware when power is restored to the system.

   
Environment: Indoor, dry
Relative Humidity: Up to 95%, non‑condensing
Temperature (operating): +32°F to +122°F (0°C to +50°C)
   
Dimensions (HxWxD): 2.0 in. x 4.5 in. x 1.3 in. (5.1 cm x 11.4 cm x 3.3 cm)
Response Time: Choice of fast (500 ms) or programmable from 1 sec to 89 sec
   
per initiating circuit:  
Alarm Current (short circuit): 40 mA maximum
Alarm Current (threshold): >25 mA
Detector Standby Current (total): 3 mA maximum
Loop Supervision Current: 8.0 mA to 15.0 mA
Trouble Current Threshold: <7 mA
Voltage (supply): 18.0 VDC to 25.5 VDC
per FPC‑7034 module:  
Current (standby): 60 mA maximum
Current (alarm): 160 mA maximum