FPD‑7024 v1.03 Fire Alarm Control Panels

FPD‑7024 v1.03 Fire Alarm Control Panels

  • Four initiating zones (expandable to eight); up to 20 two‑wire smoke detectors per zone
  • Programmable through keypads or remote programming software (RPS) through a Conettix interface module
  • Two notification appliance circuits (NACs) on board with a shared internal regulated 24 VFWR, 4 A NAC power supply
  • Easily converts to addressable with the addition of a D7039 Multiplex Expansion Module

The FPD‑7024 Fire Alarm Control Panels (FACPs) can be used in commercial and public building applications such as schools, universities, manufacturing plants, and health care facilities. They are listed by UL for central station, local, auxiliary, and remote station systems. The FPD‑7024 FACPs support four on‑board initiating zones that can be expanded to eight using the FPC-7034. Each initiating zone supports two‑wire and four‑wire detectors configurable as Class A , Style D or Class B, Style B loops. Each zone can support up to 20 two‑wire detectors, or any number of four‑wire detectors depending on available power. Each FACP has a built‑in digital fire alarm communicator transmitter (DACT).

   
Current (alarm)*: 380 mA
Current (standby)*: 200 mA
Power (primary): 120 VAC , 1.2 A maximum, 60 Hz or 240 VAC , 0.75 A maximum, 50 Hz
* For product‑specific current values, see the product’s Installation Instructions.  
   
Environment: Indoor, dry
Relative Humidity: Up to 95%, non-condensing
Temperature (operating): +32°F (0°C) to +120°F ( +49°C)
   
Color: Red
Dimensions (HxWxD): 20.8 in. x 15 in. x 4.3 in. (52.8 cm x 38.1 cm x 10.9 cm)
Material: Cold-rolled steel Base: 18 gauge (1.2 mm) Cover: 19 gauge (1.1 mm)
   
Current: 44 mA maximum per loop
Line resistance: 150 Ω
Voltage: 24 VDC nominal
   
NAC: 24 VDC nominal, 4 A maximum
On-board Relays: Three Form C contacts rated at 5 A, 28 VDC
Off-board Relays: Up to two D7035 Octal Relay Modules with each providing eight Form C relay outputs; contacts rated at 5 A, 28 VDC In an addressable system, up to 20 D7053 Multiplex Input-Output Modules are allowed per bus for a total of 40