The modules provide a supervised polarity reversal output used for audible and visual signaling devices or to trigger a remote NAC power expander. They require a 24 VDC auxiliary input voltage that can be provided by the FPA‑1000 Analog Addressable Fire Panels or other UL listed power supplies. The modules provide a Class B Circuit rated for 2 A at 24 VDC. They fit into a standard 4‑inch square or double‑gang electrical back box.
Voltage | |
Input: | 25.3 VDC to 39 VDC |
Auxiliary Input: | 24 VDC |
Current Consumption | |
FLM‑325‑NA4: | Typical: 0.22 mA Maximum: 6 mA |
FLM‑325‑NAI4: | Typical: 0.42 mA Maximum: 6 mA |
Maximum Output: | 2 A at 24 VDC, power‑limited |
SCI | |
Fault Detection Threshold: | 12 V typical |
Isolation Current: | 10 mA typical |
Operating Temperature: | +32°F to +120°F (0°C to +49°C) |
Relative Humidity: | Up to 90 %, non‑condensing |
Dimensions (H x W x D): | 4.7 in. x 4.2 in. x 1.4 in. (11.9 cm x 10.7 cm x 3.6 cm) |
Bicolored LED: | Red and green |