Bosch EVAX System - High-rise Applications

Bosch EVAX System - High-rise Applications

  • Master panel with capability for multiple distributed panels
  • Operates as stand‑alone or connected to an FACP
  • Network transmission over fiber optic or copper pair cable
  • Digitized live voice and prerecorded messaging
  • Zone paging control
  • Fan and damper control
  • Meets area of refuge/rescue assistance communication requirements
  • Variety of accessories available for system customization

The Bosch EVAX System for high-rise applications is a networked emergency relocation and paging system with integrated two‑way fireman’s telephone system. It operates with the Fire Alarm Control Panel (FACP) in a building to provide automatic response to life safety emergencies. While providing all necessary features for an effective voice evacuation system, it can easily convey evacuation, stay-in-place, or other public address announcements and automatic messages with multiple channels of simultaneous audio

   
Communication Type: RS‑485 standard
Data Rate: 1 MB
Frequency: 1.024 MHz
Wire Type: Twisted pair, Category 5 UTC
Current: 50 mA maximum
Impedance: 120 Ω maximum between panels
Voltage (peak to peak): 5 V maximum
   
Current Draw  
ASC: Alarm: 30 mA, Standby: 30 mA
DCC: Alarm: 80 mA, Standby: 80 mA
IOI: Alarm: 20 mA, Standby: 20 mA
MMC: Alarm: 45 mA, Standby: 45 mA
SLC: Alarm: 6 mA, Standby: 6 mA
SSC: Alarm: 25 mA, Standby: 25 mA
Batteries1  
Type: Two 12 VDC Gel Cell in series
Current (battery charging): 800 mA
Current (input): Typical Load: 0.28 A Maximum Load: 0.4 A
Capacity: Minimum: 24 VDC, 7 Ah Maximum: 24 VDC, 18 Ah
Power  
Input (primary): 120 VAC at 60 Hz
Input current: 0.28 A at 120 VAC
Input (circuits): all circuits at 24 VDC
   
Current Draw  
AMI: Alarm: 10 mA, Standby: 10 mA
DCC: Alarm: 55 mA, Standby: 55 mA
MBR: Alarm: 55 mA, Standby: 10 mA
Batteries2  
Type: Two 12 VDC Gel Cell in series
Current (battery charging): Depends on amplifier; EVX‑25E/50E: 800 mA maximum EVX‑100E: 1 A maximum
Capacity: Depends on amplifier; EVX‑25E/50E: 24 VDC, 18 Ah maximum EVX‑100E: 24 VDC, 24 Ah maximum
Power  
Input (primary): 120 VAC
Input current: Depends on panel configuration.
Input (circuits): all circuits at 24 VDC
   
Enclosure  
Color: Charcoal grey
Dimensions (h x w x d): 27 in x 14.5 in x 4 in (685.8 mm x 368.3 mm x 101.6 mm)