The FCS‑320-TP Series Aspirating Smoke Detectors are are active fire detection systems for early fire detection in area and equipment monitoring, as well as for the monitoring of air conditioning units or ducts. They have the latest detection technology. Their resistance to contamination, the temperature compensation of the sensor signals and initialization in relation to air pressure ensure reliable operation even under extreme environmental conditions.
|
|
Operating voltage |
14 V DC to 30 V DC |
Current consumption from auxiliary power supply (at 24 V) |
FCS-320-TP1 , FCS-320-TP2 |
Starting current, fan voltage 6.9 V |
300 mA , 330 mA |
Starting current, fan voltage 9 V |
300 mA , 330 mA |
In standby, fan voltage 6.9 V |
200 mA , 230 mA |
In standby, fan voltage 9 V |
260 mA , 310 mA |
On alarm, fan voltage 6.9 V |
230 mA , 290 mA |
On alarm, fan voltage 9 V |
290 mA , 370 mA |
|
|
Displays on the device |
|
FCS-320-TP1 / FCS-320-TP2 |
|
In operation |
Green LED |
Malfunction |
Yellow LED |
Alarm |
1 red LED / 2 red LEDs |
Conical duct connections for Ø 25 mm |
|
Aspiration pipe |
1 pipe / 2 pipes |
Air return |
1 pipe |
Cable bushings |
5 x M 20 and 2 x M 25 |
Dimensions (W x H x D) |
200 x 292 x 113 mm |
Housing material |
Plastic (ABS) |
Housing color |
Papyrus white, RAL 9018 |
Weight |
Approx. 1.5 kg |
|
|
Protection class as per EN 60529 |
IP 20 |
Permissible temperature range |
|
FCS-320-TP Series Aspirating Smoke Detectors |
-20 °C to +60 °C |
Pipe system PVC |
00 °C to +60 °C |
Pipe system ABS |
-40 °C to +80 °C |
Permissible relative humidity(non-condensing) |
10 to 95 % |
Acoustic power level |
45 dB(A) |
Response sensitivity |
max. light obscuration |
Detector Module DM-TP-50(80) |
0.5 %/m (0.8 %/m) |
Detector Module DM-TP-10(25) |
0.1 %/m (0.25 %/m) |
Detector Module DM-TP-01(05) |
0.015 %/m (0.05 %/m) |
Service life of the fan (12 V) |
43,000 hrs at 24 °C |