The Conventional Manual Call Points for Ex Areas are used to manually activate the alarm in zones 1 and 2 at risk of explosion. The K type call points are encapsulated, intrinsically safe call points and do not require any safety barriers. The DM 1103 B‑Ex Manual Call Points for ex zones must be connected via a Safety Barrier SB 3 incl. Input/Output Module DCA1192 (see system overview).
|
Operating voltage |
24 V DC |
Switch contact |
Type 366 (encapsulated), II 2 G EEx d II C |
Maximum contact load |
5 A / 250 V AC 0,25 A / 250 V DC |
Cable entry |
1x M16 x 1.5 tightening diameter 4‑8 mm, EEx e II Blind plug: 1x M16 x1.5 EEx e II |
Housing material |
Polyester, glass fiber reinforced |
Colors |
Red, RAL 3001 |
Dimensions (W x H x D) |
136 x 138 x 88 mm |
Weight |
Approx. 1800 g |
Protection class as per EN 60529 |
IP 66 |
Permissible operating temperature |
-25 °C to +40 °C |
Ex classification |
Eex emd IIC T6 |
Test certificate / PTB No. |
97-37001 |
ATEX approval no. |
PTB 97 ATEX 3197 |
Operating voltage |
16V DC to 28V DC |
Cable duct |
PG11 screws (2x) |
Connection terminals |
0.2 mm to 1.5 mm |
Housing material |
Plastic, PC |
Color |
Red, RAL 3000 |
Dimensions (W x H x D) |
134.4 x 134.4 x 43.5 mm |
Weight |
Approx. 200 g |
Protection class as per EN 60529 |
IP 54 |
Permissible operating temperature |
-25 °C to +60 °C |
Permissible storage temperature |
-30 °C to +75 °C |
Permissible relative humidity |
≤100% at T≤34 °C |
Ex classification |
EEx ib IIC T4 |
|
|
Input voltage Ui (V) |
≤ 28 |
Input current li (mA) |
≤ 100 |
Input power Pi (mW) |
≤ 700 |
Internal inductivity Li (mH) |
0 |
Internal capacity Ci (nF) |
0 |