for extension of the FPA‑5000 with the Panel Controller MPC version A
Input voltage | 20 V DC to 30 V DC 5 V DC ± 5% |
Current consumption | |
Standby | 31 mA (at 24 V DC) |
Fault | 40 mA (at 24 V DC) |
Voltage outputs | |
3 outputs, switchable | +24 V / 1.7 A, battery-buffed (programmable) |
3 outputs, not switchable | +24 V / 0.5 A, battery-buffered |
Capacity of the outputs BAT FAULT, AC FAULT | max. 500 mA (at 27 V DC) |
Maximum current to the panel rails (PRS 0002 A/PRD 0004 A) | Max. 6 A via the BCM 0000 A Max. 8 A via the batteries |
Operating/display elements | |
1 green LED | Power ON |
3 yellow LEDs | Trouble mains/batt. 1/batt. 2 |
1 key | Batteries charge at V < 22 V and central units start with battery current |
Housing material | ABS plastic, Polylac PA-766 (UL94 V‑0) |
Housing color | Satin finish, anthracite, RAL 7016 |
Dimensions | Approx. 127 x 96 x 60 mm(5.0 x 3.8 x 2.4 in.) |
Weight | |
Without packaging | Approx. 185 g (6.5 ounces) |
With packaging | Approx. 335 g (11.8 ounces) |
Permitted operating temperature | -5 °C to 50 °C (23 °F ... 122 °F) |
Permitted storage temperature | -20 °C to 60 °C (-4 °F ... 140 °F) |
Permitted relative humidity | 95%, non-condensing |
Protection class as per IEC 60529 | IP 30 |