FPP-5000-TI Trouble interface

FPP-5000-TI Trouble interface

  • Installation and auto-detection by simply inserting the modul into the Panel Rail
  • Fault message transfer of mains fault signal and battery fault signal via Local SecurityNetwork LSN.

The FPP‑5000‑TI is an extension for the FPP‑5000 External Power Supply Unit Kit 24 V/6 A. It provides the fault message transfer of the mains fault signal and the battery fault signal to the fire panel via the Local SecurityNetwork LSN. The two fault messages are provided by the corresponding outputs at the BCM 0000 A Battery Controller Module. The module is directly connected to the LSN data bus and is also power supplied via the LSN data bus line.

 
Input voltage (min - max) 15 V DC to +33 V DC
Maximum current consumption 1.15 mA at 24 V DC (from LSN)
   
Address setting Via eight DIP switches
Housing material and color ABS plastic, (UL94 V-0), semi-gloss anthracite, RAL 7016
Dimensions (W x H x L) Approx. 127 x 96 x 60 mm (approx. 5.0 x 3.8 x 2.4 inches)
   
Protection type as per IEC 60529 IP 20
Permissible operating temp. -5 °C to 50 °C (23 °F to 122 °F)
Permissible storage temp. -20 °C to 60 °C (-4 °F to 140 °F)
Relative humidity Max. 95% non‑condensing